Section 2.2.1 Connecting to an Advant Controller 410 Subsystem
3BUR 001 085R0001 REV A 2-9
The last SHIM in the RS-485 bus must have a 100-ohm 1/8W resistor inserted across
XTB1-8 and XTB1-9 to terminate the RS-485 bus.
The SHIM-4/8 is also configured to be 9600 baud, 8N1 which is its default setting. The SW2 1-
8 settings are OFF, OFF, ON, OFF, ON, ON, OFF, OFF.
The SHIM PROM version was 3.03.
Always refer to the documentation that comes with the equipment for more information.
Figure 2-5. Black Box IC108A to SHIM RS-485 Wiring Diagram
Figure 2-6. Westermo Teleindustri AB MA-42 to SHIM RS-485 Wiring Diagram
IC108A - TB1
TxA
TxB
RxA
RxB
8
9
8
9
SHIM - XTB1 SHIM - XTB1
100-ohm
Termination resistor
Internal
Termination
DATA+
DATA-
1200 meters maximum
1 meter minimum
MA-42 Line Connection
1
2
3
4
8
9
8
9
SHIM - XTB1 SHIM - XTB1
100-ohm
Termination resistor
Internal
Termination
DATA+
DATA-
1200 meters maximum
1 meter minimum